Eaton xPole PFIM four-pole RCCB rated at 80A with 300mA Type A residual current sensitivity. Suited to residential and commercial distribution boards where four-pole residual current protection is required.
Type A detects both sinusoidal AC and pulsating DC fault currents. Non-delayed tripping. Mounts on DIN rail per IEC/EN 60715, occupying 4 standard modules.
- Rated current: 80A
- IΔn: 300mA, Type A
- Breaking capacity: 10kA
- Voltage: 230V AC / 400V AC, 50Hz
- Terminal capacity: 1.5–35mm² solid, 1.5–16mm² stranded
- Operating temperature: -25°C to +60°C (derate above 40°C)
- IP20 (IP40 with suitable enclosure)