ADB516G

RCBO vs RCD: Which One Do You Need? (Irish Guide)

RCDs and RCBOs both trip when current leaks to earth. The difference is what else they do, and how much of the house goes off when one trips. This guide covers what each device does, how they are rated, and where each fits on an Irish board.

In Ireland, installations are designed to I.S. 10101, the National Rules for Electrical Installations, not to the UK’s BS 7671. NSAI published I.S. 10101:2020 in March 2020, and new installations have had to be designed to it since 1 February 2021. Amendment A1 was published in September 2024, and the current edition is I.S. 10101:2020+A1:2024/AC2:2025.

This is a general product overview, not installation or design guidance. I.S. 10101 and the manufacturer’s datasheet are the authority on selection and installation. Work on a distribution board in a home is Restricted Electrical Works and must be carried out by a Safe Electric Registered Electrical Contractor.

MCB, RCCB and RCBO: what each one does

  • MCB (miniature circuit breaker). Protects a circuit against overload and short circuit. It does not detect earth leakage.
  • RCCB (commonly called an RCD). Monitors the current flowing on the circuits it covers. If current goes astray, for example through a person, it disconnects within milliseconds. It gives no overload protection, so on a split-load board one RCCB feeds a group of MCBs.
  • RCBO. Combines the two in one device: earth leakage protection and overcurrent protection for a single circuit. Hager points out that an RCBO takes up less space than a separate RCD and MCB.

Strictly, an RCBO is also a type of RCD. On the counter, “RCD” usually means the RCCB that protects a bank of circuits.

Quick comparison

MCB RCCB (RCD) RCBO
Overload and short-circuit protection Yes No, needs MCBs after it Yes
Earth leakage protection No Yes Yes
Circuits covered One Usually a group One
Trip curve (B, C) Yes Not applicable Yes
RCD type (A, F, B etc.) Not applicable Yes Yes

Reading the ratings

  • Current rating (e.g. 6A, 16A, 32A, 40A). What the circuit is designed to carry. The electrician chooses it to suit the cable and the load.
  • Trip curve. Safe Electric gives Type B as general purpose, with instantaneous tripping at 3 to 5 times rated current (In), and Type C at 5 to 10 times In. C curves suit loads with a higher inrush, such as motors, and turn up in homes as well as commercial work. The curve letter is part of the device name, for example “B-10A” or “C-16A”.
  • Breaking capacity. The fault current the device can safely interrupt. Domestic MCBs and RCBOs are commonly 6kA or 10kA. For example, Hager’s MBN132W MCB is 6kA and its ADA510D RCBO is 10kA.
  • Sensitivity. For the RCD part, 30mA is the usual rating for additional protection. I.S. 10101 now requires it on domestic lighting circuits (Rule 411.3.4). Other ratings are used for particular jobs. Rule 551.9.3, as amended in 2024, changed the RCD at a microgenerator input from 30mA to 100mA.

Don’t confuse a B curve with a Type B RCD. The first is about overcurrent tripping, the second about the kind of leakage current detected. An RCBO can be both B curve and Type A.

RCD types: AC, A, F and B

The type tells you what kind of leakage current the device can detect.

  • Type AC: AC sinusoidal residual current only. Safe Electric’s summary of I.S. 10101 changes states that Type AC RCDs are not recommended in new installations (Clause 531.3.3).
  • Type A: everything Type AC detects, plus pulsating DC. Hager Ireland lists it for loads such as washing machines that are not frequency-controlled, induction hobs, and EV charging where the charger has built-in 6mA DC fault detection.
  • Type F: everything Type A detects, plus high-frequency residual current.
  • Type B: everything Type F detects, plus smooth DC. Hager Ireland lists it for PV, speed-control inverters and EV charging where DC fault current can be over 6mA.

For an EV charger, the charger’s documentation states whether 6mA DC fault protection is built in. That decides whether Type A or Type B is needed on the circuit. The rewritten Part 722 also requires selectivity between the RCD protecting an EV charging point and any RCD upstream of it.

Lighting circuits and RCD protection

Rule 411.3.4 requires additional protection by an RCD of not more than 30mA on a.c. final circuits supplying luminaires in domestic premises.

Safe Electric recommends a separate 6A RCBO for each lighting circuit as the ideal way to meet this rule. Hager Ireland’s guide also recommends not mixing lighting and socket circuits on the same RCD.

The Rules require RCD protection in other places too, and your electrician designs to the full text. Installations wired to earlier editions may not meet the current Rules in every respect, which doesn’t necessarily mean they are unsafe.

Split-load board or all-RCBO board

Split-load board. One or more RCCBs each protect a group of MCBs. An earth fault on one circuit trips the RCCB, and every circuit behind it goes off. Spreading circuits sensibly across the RCCBs limits how many are affected.

All-RCBO board. Each outgoing circuit has its own RCBO, so an earth fault only takes out that one circuit, and it’s obvious which circuit has the fault.

Mixed boards. Many boards use RCBOs for some circuits, such as lighting, and RCCB-protected groups for others.

Pole configurations

  • 1P, one module (17.8mm). For example Hager ADC416U, C16, 10kA, Type A.
  • 1P+N, two modules (35mm). For example Hager ADA510D, B10, 10kA, Type A.
  • 4P, four modules. For example Hager ADM410C, B10, 6kA, for three-phase circuits.

Neutral connection differs between designs, so check the datasheet, and check the RCBO is approved for the board it’s going into.

Who can fit them

In a home, modifying or replacing a distribution board and installing or replacing circuits are Restricted Electrical Works. Safe Electric defines these as works “that can only be carried out and must be certified by a Registered Electrical Contractor (REC)”. Swapping an MCB for an RCBO in a house is a job for a registered contractor, not DIY.

FAQ

What is a 40 amp RCBO used for? A single circuit designed for up to 40A that needs both overcurrent and earth leakage protection, such as some electric showers or cookers. The appliance manufacturer’s instructions give the protective device rating for each model, and the electrician sets it to suit the appliance, cable and installation.

Can I replace an MCB with an RCBO? Often, if the RCBO is compatible with the board and matches the circuit’s rating, curve and breaking capacity. In a home it’s work on the distribution board, so a Safe Electric registered contractor must do it.

Is an RCBO better than an RCD? An RCBO protects one circuit against overcurrent and earth leakage, so a fault only trips that circuit. An RCCB protects a group of circuits against earth leakage and needs MCBs after it. An electrician will pick based on the board and the circuits.

Do I need a Type A or Type AC RCBO? Type AC is not recommended in new installations. Type A also detects pulsating DC, which suits most modern appliances. Some EV chargers and PV systems need Type B, so check the equipment instructions.

Why does my RCD keep tripping? It has detected an imbalance, usually current leaking to earth on one of the circuits it protects. Small leakages from several appliances can also add up and trip it. Have a registered electrical contractor find the cause rather than resetting it again and again.