Mx1

Photo is representative

Megger MFT-X1 Multifunction Tester (1012-223)

Product Information

Stock Code 1012223
GTIN 5036175239964
Stock status: 1 available for delivery

priced individually

More arriving soon

Net price: €1507.82

Gross price

€1854.61

Branch Stock

Monaghan

Stock status: Out of stock
Closed · Opens Fri 8:00 AM
Address & hours
Monaghan, Plantation Road, Co. Monaghan, H18 E781, Ireland
+353 47 81135
Mon – Thu
8:00 AM – 6:00 PM
Fri
8:00 AM – 5:00 PM
Sat
9:00 AM – 1:00 PM
Sun
Closed

Cavan

Stock status: Out of stock
Closed · Opens Fri 8:00 AM
Address & hours
Cavan, Unit 7, Kilmore Business Park, Dublin Road, Co. Cavan, H12 PV48, Ireland
+353 49 4365190
Mon – Thu
8:00 AM – 6:00 PM
Fri
8:00 AM – 5:00 PM
Sat
9:00 AM – 1:00 PM
Sun
Closed

Carrickmacross

Stock status: 1 in stock
Closed · Opens Fri 8:00 AM
Address & hours
Carrickmacross, Ardee Rd, Co. Monaghan, A81 Y573, Ireland
+353 42 9663322
Mon – Thu
8:00 AM – 6:00 PM
Fri
8:00 AM – 5:00 PM
Sat
9:00 AM – 1:00 PM
Sun
Closed
Fast dispatch from stock
Mon–Fri
Free delivery over €61.50
Usually 1–3 working days
28-day returns
On unused items
Secure checkout Visa Mastercard American Express Google Pay PayPal Revolut Pay Klarna Amazon Pay MobilePay

The Megger MFT-X1 is a firmware-upgradeable multifunction tester for low voltage installations, covering commissioning, periodic inspection and fault finding on single and three-phase systems, including EV charge points and domestic PV. Loop testing uses True Loop™ 2-wire and 3-wire non-trip technology with the Confidence Meter™, giving 0.001 Ω resolution in high-resolution mode and 50 kA fault current calculation. Insulation testing runs at 50, 100, 250, 500 and 1000 V DC plus a variable 50–999 V, with a stabilised output of -0% +2% +2 V. RCD testing covers Types AC, A, B and their S variants, 6 mA RDC devices, configurable auto-sequences and ramp tests from 10 mA to 1000 mA. Earth testing includes 2-wire, 3-wire, ART and stakeless methods. Results transfer by Bluetooth® to CertSuite™. The MFT-X1 is rated CAT III 600 V / CAT IV 300 V, housed to IP54 and powered by a 4400 mAh Li-ion battery pack.

Specifications

Insulation Test

50, 100, 250, 500, 1000 V DC + variable 50–999 V; 0.001–999 MΩ

Insulation Output Voltage

Stabilised, -0% +2% +2 V

Continuity

0.01 Ω – 999 kΩ, >200 mA test current

Loop Impedance

True Loop 2-wire and 3-wire non-trip; 0.001 Ω high-resolution mode; 48–550 V AC

Fault Current Calculation

Up to 50 kA

RCD Testing

Type AC, A, B, AC(S), A(S), B(S); ramp 10–1000 mA; configurable auto-sequence

RDC Testing

6 mA RDC (EV charge points)

Earth Resistance

2-wire, 3-wire, ART and stakeless; 0.01–1999 Ω

Voltage Measurement

0–600 V AC TRMS; 0–1000 V DC

Measurement Category

CAT III 600 V / CAT IV 300 V (IEC 61010)

Ingress Protection

IP54

Battery

Li-ion 7.2 V 4400 mAh, >15 h typical use

Frequently asked questions

Q: Can the MFT-X1 test EV charge points?

A: Yes. It supports Type B RCD and 6 mA RDC protected charge points. With the Megger EVX100 interface it controls CP and PP states automatically through a Type 2 plug for single and three-phase Mode 3 AC chargers; it can also be used with the Megger EVCA adaptor.

Q: Is the operating system of the MFT-X1 upgradeable?

A: Yes. Download the latest operating system file from Megger to a microSD card, insert it and press TEST to update automatically.

Q: What is the loop impedance measurement resolution of the MFT-X1?

A: 0.001 Ω in high-resolution mode (0.01 Ω in non-trip and high-current modes), with PFC/PSCC calculation up to 50 kA.