Sort by:

Phoenix High-current terminal block UKH 50 3009118

PRODUCT CODE: 3009118
In stock
Phoenix High-current terminal block UKH 50 3009118
  • Number of levels: 1
  • Number of connections: 2
  • Potentials: 1
  • Nominal cross section: 50 mm²
  • Colour: grey
  • Insulating material: PA
  • Flammability rating according to UL 94: V0
  • Rated surge voltage: 8 kV
  • Degree of pollution: 3
  • Overvoltage category: III
1 Day
€ 13.43

DESCRIPTION

Specifications:
  • Insulating material group: I
  • Maximum power dissipation for nominal condition: 4.73 W
  • Maximum load current: 150 A (with 50 mm² conductor cross section)
  • Nominal current IN: 150 A
  • Nominal voltage UN: 1000 V
  • Open side panel: No
  • Shock protection test specification: DIN EN 50274 (VDE 0660-514):2002-11
  • Back of the hand protection: guaranteed
  • Finger protection: guaranteed
  • Result of surge voltage test: Test passed
  • Result of power-frequency withstand voltage test: Test passed
  • Power frequency withstand voltage setpoint: 2.2 kV
  • Result of the test for mechanical stability of terminal points (5 x conductor connection): Test passed
  • Result of flexion and pull-out test: Test passed
  • Bending test rotation speed: 10 rpm
  • Bending test turns: 135
  • Tensile test result: Test passed
  • Result of tight fit on support: Test passed
  • Tight fit on carrier: NS 32/NS 35
  • Setpoint: 10 N
  • Result of voltage-drop test: Test passed
  • Result of temperature-rise test: Test passed
  • Requirement temperature-rise test: Increase in temperature ≤ 45 K
  • Short circuit stability result: Test passed
  • Conductor cross section short circuit testing: 50 mm²
  • Short-time current: 6 kA
  • Result of thermal test: Test passed
  • Proof of thermal characteristics (needle flame) effective duration: 30 s
  • Relative insulation material temperature index (Elec., UL 746 B): 130 °C
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)): 130 °C
  • Static insulating material application in cold: -60 °C
  • Surface flammability NFPA 130 (ASTM E 162): passed
  • Specific optical density of smoke NFPA 130 (ASTM E 662): passed
  • Calorimetric heat release NFPA 130 (ASTM E 1354): 28 MJ/kg
  • Smoke gas toxicity NFPA 130 (SMP 800C): passed
  • Fire protection for rail vehicles (DIN EN 45545-2): R22 HL 1 - HL 3
  • Bending test conductor cross section/weight:
    • 25 mm² / 4.5 kg
    • 50 mm² / 9.5 kg
Note:
Regarding shock protection Finger-safe protection is not guaranteed if bridges are positioned.