Sort by:

Phoenix Feed-through Terminal Block UT 10 3044160

PRODUCT CODE: 3044160
In stock
Phoenix Feed-through Terminal Block UT 10 3044160
  • Number of levels: 1
  • Number of connections: 2
  • Potentials: 1
  • Nominal cross section: 10 mm²
  • Colour: Grey
  • Insulating material: PA
  • Flammability rating according to UL 94: V0
1 Day
€ 1.76

DESCRIPTION

Specifications:
  • Number of levels: 1
  • Number of connections: 2
  • Potentials: 1
  • Nominal cross section: 10 mm²
  • Colour: Grey
  • Insulating material: PA
  • Flammability rating according to UL 94: V0
  • Rated surge voltage: 8 kV
  • Degree of pollution: 3
  • Overvoltage category: III
  • Insulating material group: I
  • Maximum power dissipation for nominal condition: 1.82 W
  • Maximum load current: 76 A (with 16 mm² conductor cross section)
  • Nominal current IN: 57 A
  • Nominal voltage UN: 1000 V
  • Open side panel: Yes
  • Shock protection test specification: DIN EN 50274 (VDE 0660-514):2002-11
  • Back of the hand protection: guaranteed
  • Finger protection: guaranteed
  • Result of surge voltage test: Test passed
  • Surge voltage test setpoint: 9.6 kV
  • Result of power-frequency withstand voltage test: Test passed
  • Result of the test for mechanical stability of terminal points (5 x conductor connection): Test passed
  • Result of flexion and pull-out test: Test passed
  • Bending test rotation speed: 10 rpm
  • Bending test turns: 135
  • Tensile test result: Test passed
  • Conductor cross section tensile test: 0.5 mm²
  • Tractive force setpoint: 20 N
  • Conductor cross section tensile test: 10 mm²
  • Tractive force setpoint: 90 N
  • Conductor cross section tensile test: 16 mm²
  • Tractive force setpoint: 100 N
  • Result of tight fit on support: Test passed
  • Tight fit on carrier: NS 35
  • Setpoint: 5 N
  • Result of voltage-drop test: Test passed
  • Requirements, voltage drop: U1 ≤ 3.2 mV; U2 ≤ 1.5 x U1
  • Result of temperature-rise test: Test passed
  • Requirement temperature-rise test: Increase in temperature ≤ 45 K
  • Short circuit stability result: Test passed
  • Conductor cross section short circuit testing: 10 mm²