Sort by:

Eaton ELCB 4P 63A 100mA 235444

PRODUCT CODE: 235444
A few in stock

Eaton Moeller series xPole - PFIM Type AC, A, U, R RCCB. Residual current circuit breaker (RCCB), 63A, 4p, 100mA, type A, MW

  • Four Pole
  • Up to 63 Amps
  • 80x76x70mm
1 day
€ 109.35

DESCRIPTION

ELCB Four Pole 63 Amps 100 MilliAmps Eaton 235444
Product Name: Eaton Moeller series xPole - PFIM Type AC, A, U, R RCCB
Catalog Number: 235444
Model Code: PFIM-63/4/01-A-MW
EAN: 4015082354442
Product Length/Depth: 80 mm
Product Height: 76 mm
Product Width: 70 mm
Product Weight: 0.36 kg
Compliances: RoHS conform
Certifications: IEC/EN 61008
Product Specifications
Rated Operational Current for Specified Heat Dissipation (IN): 63 A
10.11 Short-Circuit Rating: Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Permitted Storage and Transport Temperature – Min: -35 °C
10.4 Clearances and Creepage Distances: Meets the product standard's requirements.
10.12 Electromagnetic Compatibility: Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method: DIN rail, Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Amperage Rating: 63 A
10.2.5 Lifting: Does not apply, since the entire switchgear needs to be evaluated.
Rated Fault Current – Max: 0.1 A
Test Circuit Range: 196 V AC - 456 V AC
10.2.3.1 Verification of Thermal Stability of Enclosures: Meets the product standard's requirements.
Tripping Time: Non-delayed
Fitted with: Interlocking device
Rated Residual Making and Breaking Capacity: 630 A
Frequency Rating: 50 Hz
10.8 Connections for External Conductors: Is the panel builder's responsibility.
Fault Current Rating: 100 mA
Terminal Protection: Finger and hand touch safe, DGUV VS3, EN 50274
Special Features: Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.8% for every 1 °C, Tripping signal contact for subsequent installation Z-NHK 248434
Sensitivity Type: Pulse-current sensitive
Ambient Operating Temperature – Max: 60 °C
Heat Dissipation Per Pole, Current-Dependent: 0 W
Climatic Proofing: 25-55 °C / 90-95% relative humidity according to IEC 60068-2
Built-in Depth: 70.5 mm
Short-Circuit Rating: 63 A (max. admissible back-up fuse)
Features: Residual current circuit breaker, Additional equipment possible
Lifespan, Electrical: 4000 operations
Connectable Conductor Cross Section (Solid-Core) – Min: 1.5 mm²
10.9.3 Impulse Withstand Voltage: Is the panel builder's responsibility.
Number of Poles: Four-pole
Terminal Capacity (Solid Wire): 1.5 mm² - 35 mm²
Ambient Operating Temperature – Min: -25 °C
10.6 Incorporation of Switching Devices and Components: Does not apply, since the entire switchgear needs to be evaluated.
Rated Short-Circuit Strength: 10 kA
10.5 Protection against Electric Shock: Does not apply, since the entire switchgear needs to be evaluated.
Used with: PFIM, Residual current circuit breakers, Type A, KLV-TC-4 276241 (Compact enclosure), Z-FW/LP 248296 (Remote control and automatic switching device), Z-RC/AK-4MU 101062 (sealing cover set)
Equipment Heat Dissipation, Current-Dependent: 10.5 W
10.13 Mechanical Function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical Impact: Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of Enclosures Made of Insulating Material: Is the panel builder's responsibility.
Static Heat Dissipation, Non-Current-Dependent: 0 W
Application: Residual current circuit breaker for residential and commercial applications, xPole - Switchgear for residential and commercial applications
10.3 Degree of Protection of Assemblies: Does not apply, since the entire switchgear needs to be evaluated.
Terminal Capacity (Stranded Cable): 16 mm² (2x)
Leakage Current Type: A
Frame: 45 mm
Built-in Width (Number of Units): 70 mm (4 SU)
Terminals (Top and Bottom): Open mouthed/lift terminals
Heat Dissipation Capacity: 0 W
Impulse Withstand Current: Partly surge-proof 250 A
Width in Number of Modular Spacings: 4
Busbar Material Thickness: 0.8 mm - 2 mm
10.2.3.2 Verification of Resistance of Insulating Materials to Normal Heat: Meets the product standard's requirements.
10.2.3.3 Resist. of Insul. Mat. to Abnormal Heat/Fire by Internal Elect. Effects: Meets the product standard's requirements.
Lifespan, Mechanical: 20000 operations
Voltage Rating: 230 V AC / 400 V AC
10.9.2 Power-Frequency Electric Strength: Is the panel builder's responsibility.
Connectable Conductor Cross Section (Solid-Core) – Max: 35 mm²
Degree of Protection: IP20, IP40 with suitable enclosure
Rated Short-Time Withstand Current (ICW): 10 kA
Accessories Required: Z-HK 248432
Pollution Degree: 2
10.7 Internal Electrical Circuits and Connections: Is the panel builder's responsibility.
Connectable Conductor Cross Section (Multi-Wired) – Min: 1.5 mm²
Rated Impulse Withstand Voltage (UIMP): 4 kV
10.10 Temperature Rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Connectable Conductor Cross Section (Multi-Wired) – Max: 16 mm²
Type: PFIM, Residual current circuit breakers, Type A
10.2.2 Corrosion Resistance: Meets the product standard's requirements.
10.2.4 Resistance To Ultra-Violet (UV) Radiation: Meets the product standard's requirements.
10.2.7 Inscriptions: Meets the product standard's requirements.
Surge Current Capacity: 0.25 kA
Permitted Storage and Transport Temperature – Max: 60 °C
Admissible Back-Up Fuse Overload – Max: 40 A gG/gL
Rated Fault Current – Min: 0.1 A
Rated Operational Voltage (UE) – Max: 400 V
Rated Insulation Voltage (UI): 440 V



RATING

IP20