Sort by:

Eaton RCD 2P 40A 30MA xPolehome 194685

PRODUCT CODE: 194685
A few in stock

Eaton Moeller series xPole - HNC RCCB. HNC, 2 pole, In: 40 A, Icn: 6 kA, I?N: 0.03 A, Type A, residential and commercial

  • 2 Poles
  • Up to 40 Amps
  • IP20
1 day
€ 33.89

DESCRIPTION

RCD 2 Pole 40Amp 30Milliamps xPolehome Eaton 194685
Product Name: Eaton Moeller series xPole - HNC RCCB
Catalog Number: 194685
Model Code: HNC-40/2/003-A
EAN: 9010238061866
Product Length/Depth: 80 mm
Product Height: 76 mm
Product Width: 35 mm
Product Weight: 0.207 kg
Compliances: RoHS conform
Certifications: IEC/EN 61008
Product Specifications
Rated Operational Current for Specified Heat Dissipation (IN): 40 A
10.11 Short-Circuit Rating: Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.4 Clearances and Creepage Distances: Meets the product standard's requirements.
10.12 Electromagnetic Compatibility: Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method: DIN rail
Amperage Rating: 40 A
10.2.5 Lifting: Does not apply, since the entire switchgear needs to be evaluated.
Rated Fault Current – Max: 0.03 A
10.2.3.1 Verification of Thermal Stability of Enclosures: Meets the product standard's requirements.
Tripping Time: Non-delayed
Fitted With: Interlocking device
Rated Residual Making and Breaking Capacity: 500 A
Frequency Rating: 50 Hz
10.8 Connections for External Conductors: Is the panel builder's responsibility.
Fault Current Rating: 30 mA
Special Features: Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for every 1 °C
Sensitivity Type: Pulse-current sensitive
Ambient Operating Temperature – Max: 60 °C
Heat Dissipation per Pole, Current-Dependent: 0 W
Built-in Depth: 45 mm
Short-Circuit Rating: 63 A (max. admissible back-up fuse)
Features: Residual current circuit breaker, Additional equipment possible
Connectable Conductor Cross Section (Solid-Core) – Min: 1.5 mm²
10.9.3 Impulse Withstand Voltage: Is the panel builder's responsibility.
Number Of Poles: Two-pole
Ambient Operating Temperature – Min: -25 °C
10.6 Incorporation of Switching Devices and Components: Does not apply, since the entire switchgear needs to be evaluated.
Rated Short-Circuit Strength: 6 kA
10.5 Protection Against Electric Shock: Does not apply, since the entire switchgear needs to be evaluated.
Used With: HNC; Type A Residual current circuit breakers
Equipment Heat Dissipation, Current-Dependent: 7.8 W, 5.8 W
10.13 Mechanical Function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical Impact: Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of Enclosures Made of Insulating Material: Is the panel builder's responsibility.
Application: Residual current circuit breaker for residential and commercial applications, xPole Home- Switchgear for residential applications
10.3 Degree Of Protection Of Assemblies: Does not apply, since the entire switchgear needs to be evaluated.
Leakage Current Type: A
Built-in Width (Number of Units): 35 mm (2 SU)
Impulse Withstand Current: Partly surge-proof 250 A
Width in Number of Modular Spacings: 2
Busbar Material Thickness: 0.8 mm - 2 mm
10.2.3.2 Verification Of Resistance Of Insulating Materials To Normal Heat: Meets the product standard's requirements.
10.2.3.3 Resist. Of Insul. Mat. To Abnormal Heat/Fire By Internal Elect. Effects: Meets the product standard's requirements.
Voltage Rating: 230 V AC
10.9.2 Power-Frequency Electric Strength: Is the panel builder's responsibility.
Connectable Conductor Cross Section (Solid-Core) – Max: 35 mm²
Degree of Protection: IP20
Rated Short-Time Withstand Current (ICW): 6 kA
Pollution Degree: 2
10.7 Internal Electrical Circuits and Connections: Is the panel builder's responsibility.
Connectable Conductor Cross Section (Multi-Wired) – Min: 1.5 mm²
Rated Impulse Withstand Voltage (UIMP): 4 kV
10.10 Temperature Rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Connectable Conductor Cross Section (Multi-Wired) – Max: 16 mm²
TYPE: HNC; Residual current circuit breakers, Type A
10.2.2 Corrosion Resistance: Meets the product standard's requirements.
10.2.4 Resistance to Ultra-Violet (UV) Radiation: Meets the product standard's requirements.
10.2.7 Inscriptions: Meets the product standard's requirements.
Surge Current Capacity: 0.25 kA
Admissible Back-Up Fuse Overload – Max: 25 A gG/gL
Rated Fault Current – Min: 0.03 A
Rated Operational Voltage (UE) – Max: 230 V
Rated Insulation Voltage (UI): 440 V



RATING

IP20